| Performance |
| Measurement Range (RH) |
0-100% RH |
| Measurement Range (T) |
-30 to +70°C / -22 to +158°F |
Accuracy at 23°C / 73°F Humidity |
<±2% RH (5-95% RH) |
Accuracy at 23°C / 73°F Temperature |
±0.4°C (-10 to +50°C) ±0.72°F (+14 to +122°F) |
| Stability - RH Sensor |
<±1% RH/year |
| Response time – RH Sensor |
<10 sec typical (for 90% of the step change) |
| Electrical output/input |
| Output Signal |
0–1 VDC, 0–5 VDC, 0–10 VDC 0–20 mA, 4–20 mA, RS485 |
| Supply Voltage |
15 ≤ VAC ≤ 27 18 ≤ VDC ≤ 38 |
| Load Resistance |
Current output: R ≤ 500 Ω |
| Power Consumption |
1.7 W |
| Operating conditions |
Operating Humidity Probe, Housing, Storage |
0–100% RH |
Operating Temperature Probe Housing Storage |
-30 to +85°C / -22 to +185°F -20 to +70°C / -4 to +158°F -30 to +70°C / -22 to +158°F
|
| Mechanical specification |
| Ingress Protection Sensor |
IP65 |
Housing Material Housing Probe |
Aluminium die casting Delrin
|
Dimensions Housing Probe |
120 x 120 x 49.5mm / 4.72 x 4.72 x 1.94" L=100mm, ø19mm / L=3.93”, ø0.74”
|
| Weight |
450g / 15.87oz |
| Electrical Connections |
Screw terminals |
| Display Resolution |
LCD, 2 lines x 16 characters |